Adjustable Double Display VA Protector

Category

Overvoltage and current protection

Under voltage protection

Automatic Reclosing

Voltage/ Current Display

Adjustable voltage, current tripping, and automatic reclosing time

Thông tin bổ sung

Product Details:

Function:

Overvoltage protection/shutdown
Undervoltage protection/shutdown
Overcurrent protection/shutdown
Continuous Overcurrent counting/shutdown
Wide voltage Overvoltage 130-300V, undervoltage 80-210V. It is always protected upon incorrect setting, and the fault lamp is on.
Rapid protection against power failure Abnormal ignition of front-end power grid, power failure, and other protector actions
Manual/ automatic recovery After manual protection turns off the output, it must be turned on manually
Knife Function When the protection function is turned off, the relay remains as it is and no longer acts, but the switch button is still active
Multi-mode display Voltage, current, frequency, visual power, etc, are switched according to mode
Setup lock Prevent the parameters from being modified mistakes, which can not achieve the purpose of protection
DC mode When DC is used, current/ power is invalid
Energy saving mode Reduce the brightness of the digital tube to save energy when the protector is not active
Embedded RTOS The system performance and stability are improved and the system has high maintainability

 

Parameters:

Effective Voltage Range AC 80 ~300 V 1%  Can be calibrated and have higher accuracy
Effective Current Range AC 0.1 ~63.0 A 1%  Can be calibrated and have higher accuracy
Frequency Range 40 ~70 Hz 1%  Can be calibrated and have higher accuracy
Screen Refresh Rate > 1000 Hz
Table Update 0.1 ~1.0 S 1% Screen value update
Table Algorithm Root mean square/ RMS This algorithm should be used in a mains power grid
Overvoltage and Undervoltage backlash 5 V Fixed 5v backlash
Timer Range 1 ~999 S 1% User settings
Action Time 0.1 ~10.0 S 1% User settings
Effective DC Range DC 80 ~300 V 1%

 

Dimensions:

Wiring Diagram:

Setting:

NO. Option code Option max min Default Step Unit Description
P1 Pt Power-on delay 999 1 5 1/10 S
P2 rt Recovery delay 999 1 30 1/10 S
P3 oU Overvoltage 300 130 270 1/10 V Close overvoltage if greater than 300
P4 oUr Overvoltage recovery value 295 125 265 1/10 V Skip this setting when overvoltage is turned off
P5 Uu Undervoltage 210 80 170 1/10 V Close Undervoltage if below 80
P6 uUr Undervoltage recovery value 215 85 175 1/10 V Skip this setting when Undervoltage is turned off
P7 Utt Overvoltage action delay 10.0 0.1 0.5 0.1/1.0 S
P8 Uad Voltage correction +10% -10% 0 0.5% V Long press setting not recommended
P9 Oc Overcurrent 63.0 1.0 63.0 0.1/1.0 A Close overcurrent if greater than 63.0
P10 Ctt Overflow as delay 10.0 0.1 1.0 0.1/1.0 S
P11 CC Continuous overcurrent counting 20 0 0 1 Times 0: Turn off counting
P12 Cad Current correction +10% -10% 0 0.5% A Long press setting not recommended
P13 Fad Frequency correction +2.5% -2.5% 0 0.1% Hz Modifying this value will affect the accuracy of the timer
P14 FPd Rapid power failure protection on off on MS
P15 dS Display mode 3 1 1 1 1: Standards
2: Manual switch
3: Automatic switch
P16 Ar Automatic reset on off on on: Self-recovery
off: Manual recovery
P17 Act Action/ knife mode on off on on: Protector working properly
off: knife mode
P18 EC Energy saving mode on off off on: open
off: Close
P19 Loc Setup lock password 999 000 112 1/10 When this value is not 112, you can only view the parameter and cannot set it

 

 

 

 

 